How the size is worked out
± 10% for a very sunny or heavily shaded room
+ 600 BTU/h per regular occupant beyond two
+ 4,000 BTU/h for a kitchen
The chart and adjustments are the sizing guidance ENERGY STAR publishes for room air conditioners. The chart assumes 8-foot ceilings. Rooms smaller than 100 sq ft are given the smallest band, 5,000 BTU/h, since that is about the smallest unit sold.
Worked example
A 12 × 14 ft bedroom is 168 sq ft, so the chart gives 6,000 BTU/h. It faces west and gets afternoon sun, adding 10% for 6,600. Three people use it regularly, adding 600 for one person beyond two: 7,200 BTU/h. The nearest common model at or above that is 8,000 BTU/h.
When the chart is not enough
- High ceilings. A room with 10 or 12 ft ceilings holds more air than the chart assumes. Consider the next size up.
- Poor insulation or many windows. A sunroom, loft conversion or top-floor flat under a hot roof gains heat far faster than an average room.
- Open-plan spaces. Air conditioners cool the space air can reach. If the room opens to a hallway or kitchen, include that area.
- Portable units. Many portable units cool less than their headline figure suggests. Newer US labels also show a lower SACC (seasonally adjusted cooling capacity) figure; size using that one.
- Whole homes. Central air conditioning is sized with a room-by-room load calculation (ACCA Manual J), not a square-foot chart.